Inspection #: 906162
Inspection Type: Mechanical Rough
Inspector: E.Wood
Result: Partial
Comment: Bathroom exhaust ducting from 1st floor bathrooms to the pool equipment room, see highlighted and initialed ducting on print M2.6, and fresh air intakes for the pool heaters, PVC ASTM D2665 and D1785, Approved. OK to cover.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/15/2026TransferBoilerRough 20BVENT SupportB-Vent is not properly supported- per manufacture install guide, IFGC 506.2 and UPC 510.7.6 (S/W)DVFP ventingSupport venting per manufacturer's required intervals.
6/15/2026TransferMechRghSee commentsSee Inspector CommentsDVFP ventingSupport venting per manufacturer's required intervals.
6/15/2026TransferMechRghSee commentsSee Inspector CommentsDVFP ventingScrews shall not penetrate inner wall of B-vent. Provide tool to remove screw(s) for inspection of screw penetration. If screws have penetrated inner wall, replacement of compromised B-vent required.
6/15/2026TransferMechRgh25Fireplace Install InstructionsProvide installation instructions for fireplaceDVFP power venterInstall guide shall be onsite for review during inspection.