Inspection #: 906143
Inspection Type: Plumbing Rough
Inspector: K.Hanson
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/29/2026TransferGasPipeComSee comments RTU intakes As per 2018 IMC 401.4 intakes shall be located not less than 10' from gas regulator vents.
6/29/2026TransferGasRgh14PipingSee commentssee commentsRooftop gas regulatorsAs per local amendment to 2018 IFGC 410.6 regulator shall be installed 2' above the roof.
4/14/2026TransferPlumbRgh14CommentsSee Inspectors CommentsTo include but not limited to H & CW serving pool restrooms & kitchenAs per 2018 UPC 609.10 hammer arrestors required to serve quick closing valves.
4/14/2026TransferGasRgh14PipingSee commentssee commentsMedium pressure gas requlatorsAs per 2018 IFGC 410.2 note 6 tee fitting shall be installed 10 pipe diameters downstream of regulator outlet.