Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 903485
Inspection Type: Service
Inspector: M.Green
Result: Partial
Comment: Corrections from 5/27/2026 resolved. Electrical service approved. Tag # 41846. Also approved: *Employee Locker Room sheet rock ceiling rough. *Pool sheetrock ceiling rough. *Exercise Room sheetrock ceiling. *Rear Courtyard underground conduits for lights at (2) east columns.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/27/2026CorrectedCorrect service item below* Available fault current calculations.Calculations are in a format that is not familiar. Some values at the same equipment seem to differ. Clarification of available fault currents at various points in the system is necessary. UPDATE: ENGINEER PROVIDED EMAIL STATING THAT THE HIGHER AVAILABLE FAULT CURRENT NUMBERS ARE A TYPO.
5/27/2026CorrectedCorrect service item below* Grounding electrode conductor to ufer.Is there a #4 CU brought to the service?
5/27/2026CorrectedCorrect service item below* Service grounding termination.#6 CU for ground rods cannot terminate under the same lug as larger stranded conductor.
5/26/2026CorrectedCorrect service item below* MDP.Rigid 90s in bottom of switch gear require a bonding bushing and jumper sized per 250.122 for 3500A breaker.
5/26/2026CorrectedCorrect service item below* Parallel feeder runs from service to main distribution panel.250.122(F)(1)(b) requires a full sized equipment grounding conductor in each parallel conduit run. Table 250.122 requires a 500KCMIL equipment ground for 3500A breaker.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS