Inspection #: 903145
Inspection Type: Service
Inspector: M.Green
Result: Correction
Comment: Green Tag inspection for permanent power. Requested by: Ryan Heaton 907-854-6593 rmh@sei-ak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/27/2026TransferCorrect service item below* Available fault current calculations.Calculations are in a format that is not familiar. Some values at the same equipment seem to differ. Clarification of available fault currents at various points in the system is necessary.
5/27/2026TransferCorrect service item below* Grounding electrode conductor to ufer.Is there a #4 CU brought to the service?
5/27/2026TransferCorrect service item below* Service grounding termination.#6 CU for ground rods cannot terminate under the same lug as larger stranded conductor.
5/26/2026TransferCorrect service item below* MDP.Rigid 90s in bottom of switch gear require a bonding bushing and jumper sized per 250.122 for 3500A breaker.
5/26/2026TransferCorrect service item below* Parallel feeder runs from service to main distribution panel.250.122(F)(1)(b) requires a full sized equipment grounding conductor in each parallel conduit run. Table 250.122 requires a 500KCMIL equipment ground for 3500A breaker.