Inspection #: 900688
Inspection Type: Plumbing Rough
Inspector: N.Jackson
Result: Approved
Comment: MP Natural Gas Rough and Test Partial Pass. See Correction. Note: Provide MOA reviewed equipment schedule for list of appliances served. Note: Test tees not installed 10 pipe diameters downstream of reg. in accordance with 2018 IFGC 410.2. Dirt leg will suffice in lieu of downstream test tee. Note: MP regulator isolated and will require a test with non-corrosive leak detection fluid at system pressure before complete approval.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/6/2026 GasPipeComSee comments Low pressure gas pipingTest of gas piping downstream of regulators required.
5/6/2026CorrectedGasPipeRghMedium Pressure TestMedium pressure gas piping requires a 60# test- UPC local amendment 23.25.1210.5.2Medium pressure gas piping60psi test required.