| Date | Status | Code | Description | Ref | Location | Comments |
| 4/14/2026 | Transfer | PlumbRgh14 | Comments | See Inspectors Comments | To include but not limited to H & CW serving pool restrooms & kitchen | As per 2018 UPC 609.10 hammer arrestors required to serve quick closing valves. |
| 4/14/2026 | Transfer | GasRgh14Piping | See comments | see comments | Medium pressure gas requlators | As per 2018 IFGC 410.2 note 6 tee fitting shall be installed 10 pipe diameters downstream of regulator outlet. |