Inspection #: 896985
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: Swimming Pool Room and adjacent Pool Equipment Room, Restrooms, Storage, Engineering Office (except west wall). Electrical wall rough approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/10/2026Transfer01See inspection comments 1st floor east guest suites1. some locations: nail plates required. 2. Line and low volt mixed in box without separation. Some locations will need additional KO seals.
3/10/2026Transfer01See inspection comments PoolWas Conductive pool shell bonding inspection performed? Provide report. Pool shell appears to be conductive, plans show bonding at this location.