| Date | Status | Code | Description | Ref | Location | Comments |
| 4/7/2026 | | Firealarm15 | Correction(s) #2 | <div>Correct the following item(s):</div><div><br></div> | | Glass door from reception to back area has a magnetic lock installed and there is no relay release from the fire alarm. |
| 4/7/2026 | | firealarm11 | Fire Alarm approved CCO | Fire Alarm approved for CCO | | Approved for CCO till 5/1/2026 |
| 4/7/2026 | | Firealarm14 | Correction(s) #1 | <div>Correct the following item(s):</div><div><br></div> | | Offices and conference room on the south side of failed to meet the required decibels AMC 23.45.<span class="bold">907.5.2.1.3 Minimum sound pressure.</span><span> The minimum sound pressure level in every occupiable space shall be 75 dBA in Group I-1 and R occupancies and 60 dBA in all other occupancies. Was obtaining reading of 54-57 dBA.</span> |