Inspection #: 896116
Inspection Type: Wall Rough Electrical
Inspector: M.Green
Result: Partial
Comment: 1st floor elevator shaft / south work room wall. Electrical rough approved. 500KCMIL CU GEC from electric room, through BCIs, to east end water line entrance into building. Approved. NOTE: 250.24(A) and 250.24(A)(1) requires that the grounding electrode conductor be connected to the grounded service conductor (neutral) at an accessible point up to the neutral bus in the service disconnect.