Click Here To View Another Inspection Inspection #: 896116 Inspection Type: Wall Rough Electrical Inspector: M.Green Result: Partial Comment: 1st floor elevator shaft / south work room wall. Electrical rough approved. 500KCMIL CU GEC from electric room, through BCIs, to east end water line entrance into building. Approved. NOTE: 250.24(A) and 250.24(A)(1) requires that the grounding electrode conductor be connected to the grounded service conductor (neutral) at an accessible point up to the neutral bus in the service disconnect. Inspection Corrections DateStatusCodeDescriptionRefLocationComments