Inspection #: 895475
Inspection Type: Plumbing Rough
Inspector: K.Hanson
Result: Correction
Comment: Partial Plumbing Rough - Approved DWV/water/gas rough & tests approved, DWV to include 1st fl piping within grid lines 5-8 & D-H, water to include 1st fl piping within grid lines 13-16 & C-A as well as corridor mains, kitchen, guest laundry & pool area, gas to include corridor main, DVFP, kitchen & guest laundry. Incomplete gas branch piping serving heat lamp(s) run to regulator location & pool mech rm/firepit piping stubbed into pool mech rm. WH mech rm & all meter connection piping incomplete.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/14/2026TransferPlumbRgh14CommentsSee Inspectors CommentsTo include but not limited to H & CW serving pool restrooms & kitchenAs per 2018 UPC 609.10 hammer arrestors required to serve quick closing valves.
4/14/2026TransferGasRgh14PipingSee commentssee commentsMedium pressure gas regulatorsAs per 2018 IFGC 410.2 note 6 tee fitting shall be installed 10 pipe diameters downstream of regulator outlet.