Inspection #: 895310
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: Electrical wall rough approved in the following 1st floor rooms: *IT Room. *Linen 1 & 2. *Linen Shute. *Laundry. *Break Room, adjacent restroom, Locker Room. *Work Room. *Office. *"The Cove." *Alcove. *Office 37. *Men's Restroom. NOTE: Feeder conduits from upper floors into an office ceiling into J-boxes (not a part of this inspection - feeder conduits not complete). Verify feeder J-box sizing and conduit entry spacings meet 314.28(A)(2). Call if questions.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/10/2026Transfer01See inspection comments 1st floor east guest suites1. some locations: nail plates required. 2. Line and low volt mixed in box without separation. Some locations will need additional KO seals.
3/10/2026Transfer01See inspection comments PoolWas Conductive pool shell bonding inspection performed? Provide report. Pool shell appears to be conductive, plans show bonding at this location.