Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 894566
Inspection Type: Fire Sprinkler Rough-In
Inspector: D.Meneses
Result: Partial
Comment: 1am if available 1st floor cover up for rooms Requested by: Josh Daly 907-306-5007 jando@yukonfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/19/2026TransferFireSprnkRoughOtherFire Sprinkler Rough Partial ApprovalFire Sprinkler Rough Partial Approval.   List area(s) approved1st floor rooms only1st floor rooms are okay to cover.
3/17/2026TransferFireSprinkRough10Correction(s) #6Correct the following item(s):2nd floor hallprovide and maintain required space between Duct and sprinkler piping.
3/17/2026TransferFireSprinkRough1Correction(s) #1Correct the following item(s):2nd floor hallProvide information for compatibility with CPVC piping. 
3/17/2026TransferFireSprnkRoughOtherFire Sprinkler Rough Partial ApprovalFire Sprinkler Rough Partial Approval.   List area(s) approved2nd floor onlyokay to cover rooms only, Hall has correction.
1/15/2026TransferFireSprinkRough11NotesNotes: ADVISORY - Main piping runs along the length of the corridor could be subject to significant thermal expansion. Adjust piping and branch line penetrations as necessary // PANILO
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS