Inspection Type: Fire Sprinkler Rough-In
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/17/2026 FireSprinkRough10Correction(s) #6Correct the following item(s):2nd floor hallprovide and maintain required space between Duct and sprinkler piping.
3/17/2026 FireSprinkRough1Correction(s) #1Correct the following item(s):2nd floor hallProvide information for compatibility with CPVC piping. 
3/17/2026 FireSprnkRoughOtherFire Sprinkler Rough Partial ApprovalFire Sprinkler Rough Partial Approval.   List area(s) approved2nd floor onlyokay to cover rooms only, Hall has correction.
1/15/2026 FireSprinkRough11NotesNotes: ADVISORY - Main piping runs along the length of the corridor could be subject to significant thermal expansion. Adjust piping and branch line penetrations as necessary // PANILO