Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 893869
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: 3rd floor - Linen Corridor, Linen, Electric Room walls. Electrical rough approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/10/2026Transfer01See inspection comments 1st floor east guest suites1. some locations: nail plates required. 2. Line and low volt mixed in box without separation. Some locations will need additional KO seals.
3/10/2026Transfer01See inspection comments PoolWas Conductive pool shell bonding inspection performed? Provide report. Pool shell appears to be conductive, plans show bonding at this location.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS