Inspection #: 892232
Inspection Type: Fire Alarm Final
Inspector: B.Meinhardt
Result: Partial
Comment: 6 am inspection at Repsol office 6th floor of ANO building POC Cody 907-230-3914

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/7/2026TransferFirealarm15Correction(s) #2<div>Correct the following item(s):</div><div><br></div> Glass door from reception to back area has a magnetic lock installed and there is no relay release from the fire alarm.
4/7/2026Transferfirealarm11Fire Alarm approved CCOFire Alarm approved for CCO Approved for CCO till 5/1/2026
4/7/2026TransferFirealarm14Correction(s) #1<div>Correct the following item(s):</div><div><br></div> Offices and conference room on the south side of failed to meet the required decibels AMC 23.45.<span class="bold">907.5.2.1.3 Minimum sound pressure.</span><span>&nbsp;The minimum sound pressure level in every occupiable space shall be 75 dBA in Group I-1 and R occupancies and 60 dBA in all other occupancies.&nbsp; Was obtaining reading of 54-57 dBA.</span>