Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/8/2026 Correct Below* New panels. Provide plans detailing AFC and date for added panels. Label panels with AFC information to include date of calculation.
1/8/2026 Correct Below* Fire pump room. Lighting shown to be battery backed em lighting. Currently not installed, standard lighting installed. Plans show 4 ea. in this area.
1/8/2026 Correct Below* Garage area. GFCI protection required for all new receptacles per 210.8. Various locations throughout.