Inspection #: 887561
Inspection Type: Ceiling Rough Electrical
Inspector: M.Green
Result: Correction
Comment: Remainder of 3rd floor guest room ceilings above sheet rock fire ceiling - electrical rough approved. Correction below has been updated but does not directly affect ceiling rough.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/12/2026TransferEC1Correct Below   
1/9/2026TransferEC1Correct Below Class 2 wiring and line voltage wiring located in unit closets.Remove Romex used for Class 2 wiring from J-box containing line voltage. Class 2 wiring exits box in closet and runs to a T-stat(?) box. Wiring from the T-stat box to other devices is not a Chapter 3 wiring method. UPDATE TO THIS CORRECTION: THE SINGLE NIPPLE RELAY IN A BOX (AS INTENDED TO BE INSTALLED) DOES NOT PERMIT SEPARATION OF LINE VOLTAGE AND CLASS 2 CONDUCTORS AS REQUIRED BY 725.136. FUNCTIONAL DEVICES (MAKER OF RIBs) MAKES THE "RIBT" SERIES THAT PROVIDES COIL CONDUCTOR SEPARATION FROM RELAY CONTACT CONDUCTOR SEPARATION VIA MULTIPLE ENTRIES.