| Date | Status | Code | Description | Ref | Location | Comments |
| 1/12/2026 | Transfer | EC1 | Correct Below | | | |
| 1/9/2026 | Transfer | EC1 | Correct Below | | Class 2 wiring and line voltage wiring located in unit closets. | Remove Romex used for Class 2 wiring from J-box containing line voltage. Class 2 wiring exits box in closet and runs to a T-stat(?) box. Wiring from the T-stat box to other devices is not a Chapter 3 wiring method. UPDATE TO THIS CORRECTION: THE SINGLE NIPPLE RELAY IN A BOX (AS INTENDED TO BE INSTALLED) DOES NOT PERMIT SEPARATION OF LINE VOLTAGE AND CLASS 2 CONDUCTORS AS REQUIRED BY 725.136. FUNCTIONAL DEVICES (MAKER OF RIBs) MAKES THE "RIBT" SERIES THAT PROVIDES COIL CONDUCTOR SEPARATION FROM RELAY CONTACT CONDUCTOR SEPARATION VIA MULTIPLE ENTRIES. |