Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 887529
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Partial
Comment: Electrical final conditionally approved to extend for 21 days.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/8/2026TransferCorrect Below* New panels. Provide plans detailing AFC and date for added panels. Label panels with AFC information to include date of calculation.
1/8/2026TransferCorrect Below* Fire pump room. Lighting shown to be battery backed em lighting. Currently not installed, standard lighting installed. Plans show 4 ea. in this area.
1/8/2026TransferCorrect Below* Garage area. GFCI protection required for all new receptacles per 210.8. Various locations throughout.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS