Inspection #: 886927
Inspection Type: Ceiling Rough Electrical
Inspector: M.Green
Result: Correction
Comment: Above sheetrock fire ceilings electrical rough inspection for the following guest rooms: 4th floor 428-443 (427 not complete). 3rd floor 301-330 on both sides of hall and 332, 334, 336, 338, 340, 342 on south side of hall. Electrical ceiling rough approved for above sheetrock fire ceilings. Correction below does not pertain to ceilings.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/9/2026TransferEC1Correct Below Class 2 wiring and line voltage wiring located in unit closets.Remove Romex used for Class 2 wiring from J-box containing line voltage. Class 2 wiring exits box in closet and runs to a T-stat(?) box. Wiring from the T-stat box to other devices is not a Chapter 3 wiring method.