Inspection #: 886790
Inspection Type: Final Plumbing
Inspector: E.Wood
Result: Correction
Comment: First floor plumbing ( less rooms 121, 124, and 125) OK, see corrections. CCO for phases 1-3 until Jan. 29th, 2026. NOTES: #1. BAT # 1314 for the water main backflow preventer, and BAT# 1220 for the 2 RPBAs in the hotel commercial laundry room. #2. Phase 4 consisting of the guest patio, and the pool, to be seen later.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/29/2025TransferPlumbFinal1WaterTempTub/Shower<em>Tub/shower water temperature is required to be between 110-120 degress fahreneit- UPC 418 and local amendment 419</em>Rooms 121, 124, 125, and 229.Trim install incomplete also over temp.
12/26/2025CorrectedPlumbFinal17Backflow Preventer RequiredAn approved backflow preventer is required-UPC 602.2Kitchen steam equipmentPer local amendment to 2018 UPC 603.5.28 ASSE 1012 listed device required.
12/26/2025TransferPlumbFinalCommentsSee Inspector CommentsPool rmPool & equipment incomplete.
12/26/2025CorrectedPlumbFinalCommentsSee Inspector CommentsHRU-201 & AHU-101 in 2nd fl mech rm, condensate terminating outside behind 1st fl mech rmCondensate incomplete/protect from freezing.