Inspection #: 886711
Inspection Type: Final Plumbing
Inspector: K.Hanson
Result: Correction
Comment: CCO for occupancy of 2nd fl given, expires 1-29-26. Partial Plumbing Final - Approved To include all rms except noted incomplete & 1-room w/ correction. NOTE: Lav install incomplete in rooms 269, 274 & 275, WC & lav install incomplete in room 266.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/29/2025TransferPlumbFinal1WaterTempTub/Shower<em>Tub/shower water temperature is required to be between 110-120 degress fahreneit- UPC 418 and local amendment 419</em>Rm 229Trim install incomplete also over temp.
12/26/2025TransferPlumbFinal17Backflow Preventer RequiredAn approved backflow preventer is required-UPC 602.2Kitchen steam equipmentPer local amendment to 2018 UPC 603.5.28 ASSE 1012 listed device required.
12/26/2025TransferPlumbFinalCommentsSee Inspector CommentsPool rmPool & equipment incomplete.
12/26/2025CorrectedPlumbFinalCommentsSee Inspector CommentsGas flexes & piping serving commercial dryersFlexes & piping undersized.
12/26/2025TransferPlumbFinalCommentsSee Inspector CommentsHRU-201 & AHU-101 in 2nd fl mech rm, condensate terminating outside behind 1st fl mech rmCondensate incomplete/protect from freezing.