| Date | Status | Code | Description | Ref | Location | Comments |
| 12/26/2025 | Transfer | PlumbFinal17 | Backflow Preventer Required | An approved backflow preventer is required-UPC 602.2 | Kitchen steam equipment | Per local amendment to 2018 UPC 603.5.28 ASSE 1012 listed device required. |
| 12/26/2025 | Transfer | PlumbFinal | Comments | See Inspector Comments | Pool rm | Pool & equipment incomplete. |
| 12/26/2025 | Transfer | PlumbFinal | Comments | See Inspector Comments | Gas flexes & piping serving commercial dryers | Flexes & piping undersized. |
| 12/26/2025 | Transfer | PlumbFinal | Comments | See Inspector Comments | HRU-201 & AHU-101 in 2nd fl mech rm, condensate terminating outside behind 1st fl mech rm | Condensate incomplete/protect from freezing. |