Inspection #: 884852
Inspection Type: Final Plumbing
Inspector: J.Bean
Result: Correction
Comment: See Correction

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/8/2025TransferPlumbFinalCommentsSee Inspector CommentsRoof DrainsFernco Couplings that are installed are not listed and labeled as flex's for rain-leader connection to roof drains. 1101.5 Expansion Joints Required. Expansion joints or sleeves shall be provided where warranted by temperature variations or physical conditions. 2018 UPC Illustrated Training Manual explanation A typical location for the installation of an expansion joint is the connection between a roof drain body attached to a plywood decked roof and a vertical conductor. Movement of the wood roof and expansion of the piping would otherwise either damage the piping or damage the water-tight joint between the roof and the roof or overflow drain.