Inspection #: 882631
Inspection Type: Framing
Inspector: thomas.green
Result: Correction
Comment: Recall for follow up inspection after framing corrections have completed.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/3/2025TransferFRAMASee Inspector commentsSee Inspector commentsNew design for 2 5/8" metal studs to support new sheetrock on meeting room ceilings. Provide field change order with detail and/or description showing stud sizing and spacing required for span in meeting rooms.
12/3/2025TransferFRAMASee Inspector commentsSee Inspector commentsNew 2 5/8" studs to support sheetrock on ceilings. Secure top of studs to track to prevent rolling.