Inspection #: 881269
Inspection Type: Mechanical Rough
Inspector: K.Hanson
Result: Correction
Comment: Partial Mechanical Rough - Approved To include all previously incomplete duct in 2nd fl Mech rm, OK to cover. See correction. NOTE: Will inspect rooftop equipment & related clearances next visit/at Final.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/1/2025TransferBoilerRough24See comments Relief valve termination (2-glycol boilers)As per 2018 UPC 305.1 & glycol manufacturer's instruction, relief valves may not terminate to FD.
10/17/2025TransferEnvAir14See comments Corridor GRDsGRDs shall be independently supported per SMACNA.
2/25/2025CorrectedMechRghSee commentsSee Inspector CommentsHoliday inn side third floor. Supply air runs supply all rooms (32)Per 2018 IMC 607.3.3 actuator valves are required to have access panels large enough for maintenance, replacement, and service. DO NOT COVER.
2/25/2025CorrectedMechRghSee commentsSee Inspector CommentsHoliday inn side third floor fire and smoke dampers rooms 304, 324, and electrical room.Per 2018 IMC 607.3.3.2 Fire and smoke dampers must be installed and inspected to conform proper clearances are maintained for the functionality of its design. Per 2018 IMC 607.4 Access and identification, all smoke and fire dampers must be properly labeled and proper access provided for maintenance and replacement. Fire dampers are not installed and not inspected DO NOT COVER.