Inspection #: 881007
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Electrical final conditionally approved for 14 days for move in.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/22/2025TransferCorrect Below* PlansProvide plans for updated AFC and date.
12/22/2025TransferCorrect Below* Plans. If methane detection at building is determined to not be required by the engineer, remove reference for installation of detectors throughout plans. Specs 28.42.00, and panel schedules showing methane detection. Change order for removal of references required.
10/29/2025CorrectedCorrect Below* Detectors.1. Per the detector literature. Detectors are for detection of Carbon monoxide and natural gas. Detectors do not appear to be for the gas that is intended top be detected. Engineer required to determine correct detector for application and submit documentation. 2. Recommended locations of detectors requires that they are placed away from air vents. Currently they are all closely mounted to the air vents for each unit. Engineer to determine correct detector and placement of. 3. UPDATE: 11/3/25. SUBMIT ENGINEERED DRAWINGS DETAILING GAS DETECTION EQUIPMENT TO BE USED. ON DRAWINGS, DETAIL MINIMUM DISTANCE REQUIRED FROM AIR VENTS PER MANUFACTURER AND ENGINEER REQUIREMENTS.