Inspection #: 880673
Inspection Type: Final Electrical
Inspector: M.Green
Result: Cancel
Comment: Cancelled. Gas detection system engineering has not been completed; proposed detectors have not been determined to be suitable. Conditional electrical final will not be approved without proper engineering and approvals from Plan Review and AFD.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/29/2025TransferCorrect Below* Detectors.1. Per the detector literature. Detectors are for detection of Carbon monoxide and natural gas. Detectors do not appear to be for the gas that is intended top be detected. Engineer required to determine correct detector for application and submit documentation. 2. Recommended locations of detectors requires that they are placed away from air vents. Currently they are all closely mounted to the air vents for each unit. Engineer to determine correct detector and placement of. 3. UPDATE: 11/3/25. SUBMIT ENGINEERED DRAWINGS DETAILING GAS DETECTION EQUIPMENT TO BE USED. ON DRAWINGS, DETAIL MINIMUM DISTANCE REQUIRED FROM AIR VENTS PER MANUFACTURER AND ENGINEER REQUIREMENTS.