| 10/29/2025 | Transfer | Correct Below | * | | Detectors. | 1. Per the detector literature. Detectors are for detection of Carbon monoxide and natural gas. Detectors do not appear to be for the gas that is intended top be detected. Engineer required to determine correct detector for application and submit documentation.
2. Recommended locations of detectors requires that they are placed away from air vents. Currently they are all closely mounted to the air vents for each unit. Engineer to determine correct detector and placement of.