Inspection #: 880235
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/29/2025CorrectedCorrect Below*  1. permanent labeling for disconnect required 2. Install numbers at panels 3. AFC and date required at panels. 4. Unique labeling for furnaces required at panel schedule. 5. Post sheet E0.3 at panel locations designating hazardous locations. 6. Duct seal raceways from passage of air and condensation between interior and exterior.
10/29/2025TransferCorrect Below* Detectors.1. Per the detector literature. Detectors are for detection of Carbon monoxide and natural gas. Detectors do not appear to be for the gas that is intended top be detected. Engineer required to determine correct detector for application and submit documentation. 2. Recommended locations of detectors requires that they are placed away from air vents. Currently they are all closely mounted to the air vents for each unit. Engineer to determine correct detector and placement of. 3. UPDATE: 11/3/25. SUBMIT ENGINEERED DRAWINGS DETAILING GAS DETECTION EQUIPMENT TO BE USED. ON DRAWINGS, DETAIL MINIMUM DISTANCE REQUIRED FROM AIR VENTS PER MANUFACTURER AND ENGINEER REQUIREMENTS.