Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 880206
Inspection Type: Electrical Rough
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/29/2025 01See inspection comments  Provide install instructions for fire rated wire.
7/3/2025 01See inspection comments Roof topflat and level working clearances required to be maintained at roof top units. Some have ducting installed, some have gas piping in working clearances.
7/3/2025 01See inspection comments Roof top.1. RMC required to roof top equipment.
1/27/2025 01See inspection comments  1. Bollards required at transformers and panels. 2. Resupport vertically hanging raceways per NEC, or demo.
12/9/2024 01See inspection comments  Provide change order with plan review for alternate equipment at service. Include Available fault current calculations for new panels and equipment.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS