Inspection #: 876064
Inspection Type: Service
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/3/2025 Correct service item below* Inspection for bollards at equipment. Remove or relocate hold down bolt out of working clearances. Tripping hazard in working clearance
10/1/2025 Correct service item below*  1. Verify and provide Full load current of pump to verify adequate OCPD protection of conductors for locked rotor current. 2. Lockable disconnect required for fire pump. See 695.4 (B)(3). 3. Ensure fire rated circuit for pump wiring within building.