| Date | Status | Code | Description | Ref | Location | Comments |
| 10/2/2025 | Corrected | Correct Below | * | | Drawings. | Show 15A fused disconnect. Contractor has installed a 15HP rated snap switch. Engineer to change drawings as discussed. |
| 10/2/2025 | Corrected | Correct Below | * | | Chiller ratings. | Approved drawings show chiller with MCA rating of 14.5A and using an existing 20A, 3-pole breaker.
Chiller nameplate shows an MCA rating of 17.6A and MOP of 25A.
Engineer needs to determine adequacy of circuit and change drawings as discussed.
|
| 10/2/2025 | Corrected | Correct Below | * | | Chiller unit listing. | Unit does not appear to have a listing label. Unit will need to be replaced or field evaluated if a valid listing label is not located on the unit. |