Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 875643
Inspection Type: Service
Inspector: E.Widman
Result: Correction
Comment: Service approved. Tag 41147.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/3/2025TransferCorrect service item below* Inspection for bollards at equipment. Remove or relocate hold down bolt out of working clearances. Tripping hazard in working clearance
10/1/2025TransferCorrect service item below*  1. Verify and provide Full load current of pump to verify adequate OCPD protection of conductors for locked rotor current. 2. Lockable disconnect required for fire pump. See 695.4 (B)(3). 3. Ensure fire rated circuit for pump wiring within building.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS