Inspection #: 875409
Inspection Type: Electrical Service
Inspector: N.Holland
Result: Approved
Comment: Install Approved TAG#37591

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/30/2025CorrectedCorrect service item below* 4 pack service1) Not properly supported existing post rotted at base. Shall be supported to Chugach ESR for remote mounted services. 2) GEC shall be established at Service by driving in ground rods and landing GEC on Neutral bar.
9/30/2025CorrectedCorrect service item below* Trailer1) Head bolt receptacle on dedicated circuit remains to added. 2) Pnl schedule shall be completed. 3) Equipment ground remains to added from service to trailer. OPTIONS: Run a new 4 wire cable, or megger test existing feeder wires if plan is just to add a ground.