| Date | Status | Code | Description | Ref | Location | Comments |
| 9/29/2025 | Transfer | Correct Below | * | | | Update permit to reflect electrical contractor performing installation. |
| 9/29/2025 | Transfer | Correct Below | * | | | Label MTS for primary generator or backup generator. |
| 7/9/2025 | Transfer | Correct Below | * | | SF-4 and EF-1. | Where are these located? |
| 7/9/2025 | Corrected | Correct Below | * | | Automatic transfer switch ATS-SC. | Verify 35KA rating or have engineer change note to accept a lesser short circuit current rating if applicable. |
| 7/9/2025 | Transfer | Correct Below | * | | Installed system if intended as an NEC Article 700 emergency system. | Labelling per 700.10(A) Identification. Panels, transfer switches, generators, conduits, etc. are required to be labelled as a part of the emergency system. |
| 7/9/2025 | Transfer | Correct Below | * | | 1-line drawing and design. | Smoke control / evacuation system may be an NEC 700, emergency system. There is a note referring to 700.3(F). Engineer needs to clearly identify type of system. |
| 7/9/2025 | Transfer | Correct Below | * | | MTS-SC. Manual transfer switch to comply with 700.3(F). | 700.3(F) requires labelling to include phase rotation and system bonding requirements. |
| 7/9/2025 | Corrected | Correct Below | * | | MTS-SC. Manual transfer switch installed to comply with 700.3(F). | Verify 4-pole transfer switch to be compatible with generator configured as separately derived system. Verify 22KA short circuit current rating as required by note on 1-line. |
| 7/9/2025 | Transfer | Correct Below | * | | Approved 1-line drawing. | Installation does not conform to 1-line drawing - from Panel SCH to transformer to panel SCL. Engineer needs to update 1-line to show installed feeder OCPD and conductor sizes, XFMR size, fused disconnect instead of main circuit breaker in Panel SCL, etc. Resubmit updated plans as change order. |