Inspection #: 874240
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Partial
Comment: Corrections made. Kitchen removed from scope of work. Phase 4 Brewery and tasting areas remain.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/24/2025TransferCorrect Below*  Phase 4 - Brewery and tasting areas incomplete.
9/24/2025CorrectedCorrect Below* Panel CPProvide panel schedule, label with sources and AFC/date. Also crimp GEC connection to transformer.
9/24/2025CorrectedCorrect Below*  Platform required at microturbine so that disconnect switch is not higher than 6'7".