Inspection #: 871214
Inspection Type: Undergound Electrical
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/4/2025 Correct electrical violation* Concrete underground J-box at northwest corner of lot.Site is on a former landfill. Site is treated like Merril Field - ground is considered to be a C1 D1 hazardous location unless engineering shows otherwise. Installation does not comply with hazardous location requirements. NOTE: There is an above ground J-box with underground conduit entries with seal-off fittings directly adjacent.