Inspection #: 868634
Inspection Type: Underground Plumbing
Inspector: K.Hanson
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/17/2026CorrectedUnGrndPlumb11Corrections as FollowsMake corrections as followsUG deck drain DWV2" required per plans.
2/17/2026CorrectedUnGrndPlumb7Improper Backfill PlasticImproper backfill for plastic, provide 3/8" pea gravel or smaller- UPC local amendment 315.0UG deck drain DWVLarge rocks in contact with exposed DWV piping.
2/17/2026CorrectedUnGrndPlumbW&V TestWaste and vent test is not holding- UPC 712.2 and 712.3UG deck drain DWVTest required, no test witnessed.