| Date | Status | Code | Description | Ref | Location | Comments |
| 8/18/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Roof to regulators | Per 2018 IFGC 406.4 A listed shutoff valve shall be installed immediately ahead of each MP regulator |
| 8/18/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Roof top regulators | Per muni amendment 410.2 When the manufacturer's instructions don't specify an installation elevation for the gas regulator, the regulator shall be installed 12 inches above the anticipated snow depth (12 inches) to protect the regulator from snow and ice buildup. So 24" total. |
| 8/18/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Rooftop unit regulators | Per 2018 IFGC 410.2
5. A tee fitting with one opening capped or plugged shall be installed between the MP regulator and its upstream shutoff valve.
6. A tee fitting with one opening capped or plugged shall be installed not less than 10 pipe diameters downstream of the MP regulator outlet. |
| 8/18/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Mens locker room shower temp at 108.5°F | Per 2018 UPC 408.3 and Muni amendment 423.0 Shower water temp to be between 110°F and 120°F |
| 8/18/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Locker room side water heater relief valve is not piped. | Per 2018 UPC 608.5 (3) Discharge pipe shall discharge independently by gravity
through an air gap into the drainage system or outside of the building with the end of the pipe not exceeding 2 feet (610 mm) and not less than 6 inches (152 mm) above the ground and pointing downwards. |