Inspection #: 867641
Inspection Type: Plumbing Rough
Inspector: J.Bean
Result: Partial
Comment: Plumbing Approved for Rough-In and Test of DWV/Water/Gas Piping, including 9 Shower valves. Correction for Hammer Arrestors to be see at Final. Gas Appliances include 2 WH's and 5 RTU's. RTU's complete, 1 GREEN TAG ISSUED.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/15/2025TransferPlumbRgh14CommentsSee Inspectors CommentsShowers2018 UPC 408.7.5 Test for Shower Receptors. Shower receptors shall be tested for water tightness by filling with water to the level of the rough threshold. The test plug shall be so placed that both upper and under sides of the sub-pan shall be subjected to the test at the point where it is clamped to the drain.
10/15/2025TransferPlumbRgh14CommentsSee Inspectors CommentsBathroomsFlushometer Valves are required to have hammer arrestors. 2018 UPC 609.10 Water Hammer. Building water supply systems where quick-acting valves are installed shall be provided with water hammer arrestors. 2018 UPC MOA Amendment 609.10 Mechanical Devices. Examples of quick-acting valve locations include, but are not limited to, dishwashers, clothes washers, toilet ballcock, icemakers, and any single handle faucet.