Inspection #: 866453
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: Final Inspection Requested by: Dylan Berg 9073507114 dberg@superiorak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/24/2025TransferCorrect Below*  3rd floor kitchen, brewery and tasting areas incomplete.
9/24/2025TransferCorrect Below* Panel CPProvide panel schedule, label with sources and AFC/date. Also crimp GEC connection to transformer.
9/24/2025TransferCorrect Below*  Platform required at microturbine so that disconnect switch is not higher than 6'7".
8/1/2025TransferCorrect Below* MDP-aLabeling required for microturbine connection on MDP to not relocate breaker. As well as 705.12 (B)(3)(2) for alternate source.
8/1/2025CorrectedCorrect Below* MDP-AOne line shows 1200 amp OCPD. main appears to be 2000 amp.
8/1/2025CorrectedCorrect Below*  Panels in lower level electrical room need labeling for panel designation and AFC/date. labeling required at shunt trips per E.04. and for alternate sources at service equipment.
8/1/2025TransferCorrect Below*  MDP-A: drain pipe in working clearance near floor of equipment.
8/1/2025CorrectedCorrect Below* Cap off unused raceways at future capstones.  
5/13/2025CorrectedCorrect Below* Phase 33 pendant lights incomplete. Fireplace incomplete.
4/30/2025CorrectedCorrect Below*  Kitchen coffee maker incomplete.