Inspection #: 865987
Inspection Type: Final Plumbing
Inspector: N.Smith
Result: Correction
Comment: Partial final. Locker room side, office side does not have hot water. See corrections. Gas piping on rooftop to new units will need to be tested again when regulators get brought up to code. Will potentially need to see backflow when sprink riser is moved. AC mini split linesets are OK - would like to see install guide for mounting.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/18/2025TransferPlumbFinalCommentsSee Inspector CommentsRoof to regulatorsPer 2018 IFGC 406.4 A listed shutoff valve shall be installed immediately ahead of each MP regulator
8/18/2025TransferPlumbFinalCommentsSee Inspector CommentsRoof top regulatorsPer muni amendment 410.2 When the manufacturer's instructions don't specify an installation elevation for the gas regulator, the regulator shall be installed 12 inches above the anticipated snow depth (12 inches) to protect the regulator from snow and ice buildup. So 24" total.
8/18/2025TransferPlumbFinalCommentsSee Inspector CommentsRooftop unit regulatorsPer 2018 IFGC 410.2 5. A tee fitting with one opening capped or plugged shall be installed between the MP regulator and its upstream shutoff valve. 6. A tee fitting with one opening capped or plugged shall be installed not less than 10 pipe diameters downstream of the MP regulator outlet.
8/18/2025TransferPlumbFinalCommentsSee Inspector CommentsMens locker room shower temp at 108.5°FPer 2018 UPC 408.3 and Muni amendment 423.0 Shower water temp to be between 110°F and 120°F
8/18/2025TransferPlumbFinalCommentsSee Inspector CommentsLocker room side water heater relief valve is not piped.Per 2018 UPC 608.5 (3) Discharge pipe shall discharge independently by gravity through an air gap into the drainage system or outside of the building with the end of the pipe not exceeding 2 feet (610 mm) and not less than 6 inches (152 mm) above the ground and pointing downwards.