| Date | Status | Code | Description | Ref | Location | Comments |
| 7/15/2025 | Corrected | PlumbRgh14 | Comments | See Inspectors Comments | Toilet | 2018 UPC 609.10 Water Hammer. Building water supply system where quick-acting valves are installed shall be provided with hammer arrestors to absorb high pressures resulting from the quick closing of these valves. Hammer arrestors shall be installed as close as possible to quick-acting valve.