Inspection #: 862319
Inspection Type: Plumbing Rough
Inspector: J.Bean
Result: Correction
Comment: See corrections, all else ok

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/8/2025CorrectedPlumbRgh14CommentsSee Inspectors CommentsWater PipingWater piping to water closet needing hammer arrestor. 2018 UPC 609.10 Building water supply systems where quick-acting valves are installed shall be provided with water hammer arrestor
8/8/2025CorrectedPlumbRgh14CommentsSee Inspectors CommentsDWV Floor drain for bathroom wet vented, wet vent not permitted in municipality, floor drain needs to be vented. 2018 UPC Local Amendment 908.2 Horizontal Wet Venting for Bathroom Groups. Delete Subsection 908.2