| Date | Status | Code | Description | Ref | Location | Comments |
| 10/29/2025 | Transfer | 01 | See inspection comments | | | Provide install instructions for fire rated wire. |
| 7/3/2025 | Transfer | 01 | See inspection comments | | Roof top | flat and level working clearances required to be maintained at roof top units. Some have ducting installed, some have gas piping in working clearances. |
| 7/3/2025 | Transfer | 01 | See inspection comments | | Roof top. | 1. RMC required to roof top equipment. |
| 1/27/2025 | Transfer | 01 | See inspection comments | | | 1. Bollards required at transformers and panels.
2. Resupport vertically hanging raceways per NEC, or demo. |
| 12/9/2024 | Transfer | 01 | See inspection comments | | | Provide change order with plan review for alternate equipment at service. Include Available fault current calculations for new panels and equipment. |