Inspection Type: Undergound Electrical
Inspector: M.Green
Result: Correction
Comment: 3/4in rigid conduit underground - extended from existing conduit to the east - to existing concrete underground J-box at northwest corner of lot by Northwood Drive. Most of the underground conduit is approved. See corrections below for issues at J-box.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/4/2025TransferCorrect electrical violation* Concrete underground J-box at northwest corner of lot.Site is on a former landfill. Site is treated like Merril Field - ground is considered to be a C1 D1 hazardous location unless engineering shows otherwise. Installation does not comply with hazardous location requirements. NOTE: There is an above ground J-box with underground conduit entries with seal-off fittings directly adjacent.
6/18/2025TransferCorrect electrical violation* PlansProvide full approved plans for review onsite to include A drawings for details about approved membrane for hazardous location. Detail should include hazardous location associated with inside of capped pilings entering the ground as well. Is there a detail for piling penetrating proposed membrane that is to block gasses from entering building?