Inspection #: 860441
Inspection Type: Electrical Rough
Inspector: O.Burbridge
Result: Correction
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/23/2025Transfer01See inspection comments Old pool area1. Nail plates needed where hole in framing member is less than 1 1/4" from face of stud. 2. Layout does not match plans. 3. Number of receptacles does not appear to meet 210.60. 4. Complete all wiring makeup. 5. Mud rings missing. 6. East portion of fitness room incomplete.
6/24/2025Corrected01See inspection comments C wing 2nd floor1. Panel schedules incomplete. 2. GFCI protection required for vending machines. 3. Loose receptacles in corridor. 4. Open neutral at receptacle in corridor.