Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 859771
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Correction
Comment: Conditional Electrical Final Approved for operation till (8/31//2025) See Corrections

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/20/2025TransferCorrect Below* Dressing Rooms lighted mirrors.Show / expose listing mark and ratings information label. UPDATE: Label does not appear to be on fixtures. Possibly will need an field evaluation from an recognized NRTL.
6/20/2025CorrectedCorrect Below* Long LED strip fixtures in back of house area.Require more than (1) seismic wire.
6/20/2025CorrectedCorrect Below* Panel schedules.Update and make accurate. Breaker designations are required to be unique, descriptive, etc.