| Date | Status | Code | Description | Ref | Location | Comments |
| 9/30/2025 | Transfer | MechComments | See comments | See comments below | No gas test was witnessed. | Test gas in accordance with IFGC 406. Generally in a retro application spraying all new fittings with soapy water while gas is turned on is acceptable. |
| 9/30/2025 | Transfer | MechComments | See comments | See comments below | Gas reg does not have test tees. | Per 2018 IFGC 410.2 - 5. A tee fitting with one opening capped or plugged shall be installed between the MP regulator and its upstream shutoff valve. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument.
6. A tee fitting with one opening capped or plugged shall be installed not less that 10 pipe diameters downstream of the MP regulator outlet. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument. The tee fitting is not required where the MP regulator serves an appliance that has a pressure test port on the gas control inlet side and the appliance is located in the same room as the MP regulator |
| 9/30/2025 | Transfer | MechComments | See comments | See comments below | Gas reg needs to be 2' above rooftop. | Per 2018 IFGC Muni amendment 410.6 Where the manufacturers instructions don't specify an installation elevation for the gas regulator, the regulator shall be install 12 inches above the anticipated snow depth to protect the regulator from snow and ice build up. |
| 9/30/2025 | Transfer | MechComments | See comments | See comments below | MAU unit is not like for like and needs a full permit to go through Muni and engineering. | |