Inspection #: 857170
Inspection Type: Electrical Rough
Inspector: O.Burbridge
Result: Correction
Comment: C wing 2nd floor. All rooms electrical final approved except for suite- rough in approved. See additional corrections for 2nd floor. Also, rooftop receptacles and fan installation from other permit is outstanding on this project.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/24/2025Transfer01See inspection comments C wing 2nd floor1. Panel schedules incomplete. 2. GFCI protection required for vending machines. 3. Loose receptacles in corridor. 4. Open neutral at receptacle in corridor.