| Date | Status | Code | Description | Ref | Location | Comments |
| 5/28/2025 | Transfer | Correct Below | * | | | Provided plans show breaker style service with arc energy reduction system. Installation is fused disconnects. Provide change order reflecting installation. |
| 5/23/2025 | Corrected | Correct Below | * | | West units | 1. Panel schedules incomplete.
2. Junction boxes need cover plates.
3. Exterior lighting incomplete on building.
4. Remove temporary wiring.
5. Provide MOA reviewed drawings with relevant change orders on site.
|