| Date | Status | Code | Description | Ref | Location | Comments |
| 8/15/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Backflow Preventor in ceiling | The drain for the backflow prevent needs to be ran to an approved location. |
| 8/15/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Ice Machines | 2018 UPC 609.10 Water Hammer. Building water supply systems where quick acting valves are installed shall be provided with hammer arrestors. 609.10.1 Local Amendment. Examples of quick acting valve locations include, but not limited to, dishwashers, clothes washers, toilet ballcock, icemaker, and any single handle faucet. |
| 8/15/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Coffee Maker | 2018 UPC 603.5.12 Beverage Dispensers. Potable water supply to beverage dispensers, carbonated beverage dispensers, or coffee machines shall be protected by an air gap or vented backflow preventer that complies with ASSE 1022 |
| 8/15/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Water Heater | 2018 UPC 507.5 Drainage Pan. ...3/4" of an inch diameter drain to an approved location |
| 8/15/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | Backflow Preventer in ceiling | Backflow Preventer to be tested and certified. 2018 UPC 603.4.2 Testing. The premise owner or responsible person shall have the backflow prevention assembly tested by a certified backflow assembly tester at the time of installation... |
| 8/15/2025 | Corrected | PlumbFinal | Comments | See Inspector Comments | 3-Compartment Sink | 3-Compartment sink needs caulked. 2018 UPC 402.2 Joints. Where a fixture comes in contact with the wall or floor, the joint between the fixture and the wall or floor shall be made watertight |